| T-Series |
 |
|
|
T1500A |
T2000A |
T2500A |
|
Compressor nominal horsepower
|
hp
|
15 |
20 |
25 |
Cooling Capacity [1] at 5° C Supply [2] (AT [3] = 5K) |
Watts |
27,000
|
37,500
|
47,000 |
Cooling Capacity at 10° C Supply (AT = 5K) |
Watts |
32,500 |
45,000 |
57,000 |
Cooling Capacity at 15° C Supply (AT = 5K) |
Watts |
39,500 |
54,000 |
68,000 |
Cooling Capacity at 20° C Supply (AT = 5K) |
Watts |
47,000 |
68,000 |
81,000 [4] |
Dry Weight |
kg |
600 |
700 |
750 |
Power Requirements |
|
415V 50Hz 3 Phase plus Neutral (4A Max) |
| Maximum Current Draw |
A/phase |
32 |
41 |
4951 |
| Power Cable (3m supplied) |
|
6mm ² 4 Core + E V75 OC |
10mm ² 4 Core + E V75 OC |
All T Series Chillers Are Supplied With a Flow Switch That Prevents Operation At Flow Rates Less Than 60L/min
|
Pressure Drop Across Chiller At 100L/min |
kPa |
30 |
20 |
15 |
At 150L/min |
65 |
40 |
25 |
At 200L/min |
115 |
75 |
45 |
At 1250L/min |
175 |
115 |
70 |
[1] All cooling capacities based on operation with 45 ° C ambient temperatures. Add 15% for operation with 35 ° C ambient temperatures.
[2] This is the temperature leaving the chiller. C
[3] D T is the temperature difference between the water entering and leaving the chiller and is dependent on the flow rate through the chiller.
[4] Exceeds operation in 45 ° C ambient temperatures, rated for 35 ° C maximum ambient.
|